Carbon monoxide warning device
Stand-alone CO monitor
- Works with or without a controller
- Range of 0-150ppm
- Three-color visual alarm indicator
- 2 preset alarms; Green=Normal, Yellow=Alarm 1, Red=Alarm 2
- Large, easy-to-read digital display
- Three power options: 115 VAC, 24 VDC, or 2 AA alkaline
- Works up to 1 year with a set of AA alkaline batteries
- Pressure compensation avoids false alarms caused by pressure changes
- Sensor cable available for remote mounting
Description of the EC-600 Cabron Monoxide Monitor
The EC-600 is a stand-alone indoor CO warning monitor. It can detect CO in a range of 0 - 150ppm. The sleek, low-profile design is equipped with a unique three-color display that changes color when CO levels reach the respective alert level. It can be operated with three different energy options; 115 VAC, 24 VDC or alkaline batteries. When CO is present, the user is notified by an audible alarm sound and the multi-color LED digital display.
The EC-600 uses a fast-reacting, low-cost plug-in electrochemical cell (electrochemical cell) cell sensor. This durable sensor can be replaced in the field without the need for special tools. The sensor can also be mounted remotely with an optional remote sensor cable.
Extension cords are available up to 20m (gradation: 3, 5, 10 or 20m).
Applications
- Clean rooms
- Laboratories
- Industrial gas plants
- Gas storage rooms
- Indoor surveillance
- Iron and steel industry
- Warehouses
- Tunnels and garages
- Automotive service areas
Specifications
|
Sampling method |
Diffusion type |
|
Principle of detection |
Potentiostatic Electrolysis Method |
|
Detection range |
0 to 150 ppm |
|
Alarm setpoints |
1st 50 ppm / 2nd 100 ppm |
|
Type of alarm |
Gas alarm / fault alarm |
|
Display of alarm |
Lights up / buzzer / display |
|
Explosion protected construction |
Non-explosion protection |
|
CE marking |
ECM / RoHS (DC specification only) |
|
Power source |
AC spec. : 100 VAC ±10 % 50/60 Hz DC spec. : 24 VDC ±10 % Dry battery spec. : AA alkaline batteries 2pcs. |
|
Continuous operation |
Approx. 1 year (25ºC, no alarm and no lighting, when using two AA alkaline dry batteries) |
|
Dimensions |
Main body: Approx. 80 (W) × 120 (H) × 35.5 (D) mm |
|
Weight |
AC : Approx. 200g |
|
Operating temperature range |
0 to 40℃ (no sudden changes) |
|
Operating humidity range |
0 to 90 %RH (no condensation) |
|
Target gas |
CO (Carbon Monoxide) |